Digital time switch can be used for
operating controls in real time.
You can easily set required program by using
four buttons.
100 Multiple programming options.
Large display will enable you to quickly
check the status and settings
Standard
program: Holiday, Cyclic, Random, Manual
Override
3 Year operational Backup
TWO separate Time Clocks in One unit
Daily, weekly program in one device,
automatic conversion summer / winter
time,
(AUTO)/constantly
or
manually
high accuracy clock/timer 1 s.
easy setting via 4 keys, clear LCD
display, min. interval 1 s.
Supply voltage: 12,24
to 240 VAC VDC 50/60 Hz.
-
Type: Relay Contacts, S.P.D.T.
Resistive (Heater) 15 Amp, 120-277 VAC
- Tungsten (Incandescent) 15 Amp @ 120 VAC, 6
Amp @ 208-277 VAC
- Ballast (Fluorescent) 8 Amp @ 120 VAC, 4 Amp
@ 208-277 VAC
- Motors 1 HP @ 120 VAC, 2 HP @ 240 VAC
- DC Loads 8 Amp @ 12 VDC, 10 Amp @ 28 VDC
- Mounts in any DIN base
Operating Voltage:
12 to 240 VAC or VDC
Start Switch Closure Time:
20 milliseconds minimum
Power Consumption:
0.7 to 3VA. AC, 0.5 to 1.7 W. DC |
Output Each
Channel
Programmable: Normal, Cyclic or Pulse
Type: Relay Contacts, S.P.D.T.
Rating: 15 Amp. resistive at 240 VAC |
Dimension: 90 x 36 x 64mm
3 x 1,4 x 2.5 Inch
Weight: 140 g , 5oz
DIN rail mounting |
Environmental Storage Temperature: -23°C to 70°C,
Operating Temperature: -20°C to 60°C |
Layout and
Dimensions
Fast Program Example
|